Skip to main content
Back

EVS-EN 60079-0:2013+A11:2014

Explosive atmospheres - Part 0: Equipment - General requirements (IEC 60079-0:2011, modified)

General information

Withdrawn from 16.07.2018
Base Documents
EN 60079-0:2011; EN 60079-0:2012; EN 60079-0:2012/A11:2013
Directives or regulations
None

Standard history

Status
Date
Type
Name
16.07.2018
Main + corrigendum
01.04.2014
Main + amendment
This part of IEC 60079 specifies the general requirements for construction, testing and
marking of electrical equipment and Ex Components intended for use in explosive
atmospheres.
The standard atmospheric conditions (relating to the explosion characteristics of the
atmosphere) under which it may be assumed that electrical equipment can be operated are:
• temperature –20 °C to +60 °C;
• pressure 80 kPa (0,8 bar) to 110 kPa (1,1 bar); and
• air with normal oxygen content, typically 21 % v/v.
This standard and other standards supplementing this standard specify additional test
requirements for equipment operating outside the standard temperature range, but further
additional consideration and additional testing may be required for equipment operating
outside the standard atmospheric pressure range and standard oxygen content, particularly
with respect to types of protection that depend on quenching of a flame such as ‘flameproof
enclosure “d”’ (IEC 60079-1) or limitation of energy, ‘intrinsic safety “i”’ (IEC 60079-11).
NOTE 1 Although the standard atmospheric conditions above give a temperature range for the atmosphere of -
20 °C to +60 °C, the normal ambient temperature range for the equipment is –20 °C to +40 °C, unless otherwise
specified and marked. See 5.1.1. It is considered that –20 °C to +40 °C is appropriate for most equipment and that
to manufacture all equipment to be suitable for a standard atmosphere upper ambient temperature of +60 °C would
place unnecessary design constraints.
NOTE 2 Requirements given in this standard result from an ignition hazard assessment made on electrical
equipment. The ignition sources taken into account are those found associated with this type of equipment, such as
hot surfaces, mechanically generated sparks, mechanical impacts resulting in thermite reactions, electrical arcing
and static electric discharge in normal industrial environments.
NOTE 3 It is acknowledged that, with developments in technology, it may be possible to achieve the objectives of
the IEC 60079 series of standards in respect of explosion prevention by methods that are not yet fully defined.
Where a manufacturer wishes to take advantage of such developments, this International Standard, as well as
other standards in the IEC 60079 series, may be applied in part. It is intended that the manufacturer prepare
documentation that clearly defines how the IEC 60079 series of standards has been applied, together with a full
explanation of the additional techniques employed. The designation “Ex s” has been reserved to indicate special
protection. A standard for special protection “s”, IEC 60079-33, is in preparation.
NOTE 4 Where an explosive gas atmosphere and a combustible dust atmosphere are, or may be, present at the
same time, the simultaneous presence of both should be considered and may require additional protective
measures.
This standard does not specify requirements for safety, other than those directly related to the
explosion risk. Ignition sources like adiabatic compression, shock waves, exothermic chemical
reaction, self ignition of dust, naked flames and hot gases/liquids, are not addressed by this
standard.
NOTE 5 Such equipment should be subjected to a hazard analysis that identifies and lists all of the potential
sources of ignition by the electrical equipment and the measures to be applied to prevent them becoming effective.
This standard is supplemented or modified by the following standards concerning specific
types of protection:
– IEC 60079-1: Gas – Flameproof enclosures "d";
– IEC 60079-2: Gas – Pressurized enclosures "p";
– IEC 60079-5: Gas – Powder filling "q";
– IEC 60079-6: Gas – Oil immersion "o";
– IEC 60079-7: Gas – Increased safety "e";
– IEC 60079-11: Gas – Intrinsic safety "i";
– IEC 60079-15: Gas – Type of protection “n”;
– IEC 60079-18: Gas and dust – Encapsulation "m";
– IEC 60079-31: Dust – Protection by enclosure “t”
– IEC 61241-4: Dust – Pressurization “pD”.
NOTE 6 Additional information on types of protection for non-electrical equipment can be found in
ISO/IEC 80079-36 (to be published).
This standard is supplemented or modified by the following equipment standards:
IEC 60079-13: Explosive atmospheres – Part 13: Equipment protection by pressurized room
“p”
IEC 60079-25: Explosive atmospheres – Part 25: Intrinsically safe electrical systems
IEC 60079-26: Explosive atmospheres – Part 26: Equipment with equipment protection level
(EPL) Ga
IEC 60079-28: Explosive atmospheres – Part 28: Protection of equipment and transmission
systems using optical radiation
IEC 62013-1: Caplights for use in mines susceptible to firedamp – Part 1: General
requirements – Construction and testing in relation to the risk of explosion
IEC 60079-30-1: Explosive atmospheres – Part 30-1: Electrical resistance trace heating –
General and testing requirements.
This standard with the additional standards mentioned above, are not applicable to the
construction of
• electromedical apparatus,
• shot-firing exploders,
• test devices for exploders, and
• shot-firing circuits.

Required fields are indicated with *

*
*
*
PDF
39.04 € incl tax
Paper
39.04 € incl tax
Browse standard from 2.44 € incl tax
Standard monitoring

Customers who bought this item also bought

Main

EVS-EN 60079-11:2012

Explosive atmospheres -- Part 11: Equipment protection by intrinsic safety "i"
Withdrawn from 16.12.2024
Main + corrigendum

EVS-EN 60079-14:2014

Explosive atmospheres -- Part 14: Electrical installations design, selection and erection
Newest version Valid from 06.10.2014
Main

EVS-EN 60079-25:2010

Explosive atmospheres - Part 25: Intrinsically safe electrical systems
Withdrawn from 15.09.2022
Main

EVS-EN 60079-15:2010

Explosive atmospheres - Part 15: Equipment protection by type of protection "n"
Withdrawn from 02.05.2019